Software: RUPS-II, Cable Part# M2502
3.4.2 Neuhaus SmartLine/Fenton PowerPal interface pinout:
Pin # | Signal Type |
1 | N/A |
2 | AC Failure (Contact Closure) |
3 | N/A |
4 | Common |
5 | Battery Low (Contact Closure) |
6 | Rx (RS232) and Turn Off UPS (Contact Closure) |
7 | Common |
8 | N/A |
9 | Tx (RS232) |
The contact closure signals are relay signals and are "normal open".
The RS232 signals are photo-transistor signals.
3.5 Para Systems Inc.
MinuteMan A-series DB-9 Interface Port
Pin # | Signal Type |
1 | Unused |
2 | AC Failure |
3 | Unused |
4 | Common (same as 7) |
5 | Low Battery |
6 | RS-232 level shutdown |
7 | Common (same as 4) |
8 | Ground level shutdown (not available on models smaller than A500) |
9 | Reserved |
Pins 2 and 5 are connected to Common when they are true.
On pin 6, an rs-232 high level (>9V) will shutdown, when running on battery.
On pin 8, shorting to ground will shutdown.
3.6 PowerCom
3.6.1 PowerCom King UPS cable Software - UPSMon-II
AC_Fail and Bat_Low - normally open (shorted to GND when active).
3.7 Exide/Deltec/Fiskars
Fiskars PowerRite Max / PowerRite Pro Cable
Fiskars PowerRite UPS Port Configuration Table
Pin # | Signal Type | Function |
1 | Basic Modem Mode; Input: RS232 high pulse 4 to 5 seconds wide | Remote UPS off: In presence of AC, Output will turn off for 15 seconds after conditionaldelay. In absence of AC, output is kept off until normal AC returns |
1 | Serial Data Mode; Input: RS232 data | RS232 serial communication input. 1200 baud, 8-bit, no parity, one stop bit, one start bit, Xon/Xoff |
2 | Basic Mode; Output: RS232 level high | AC Input failure |
2 | Serial Data Mode; Output: RS232 data | RS232 serial communication output. Same as input |
3 | Output: Open collector transistor ON, 50 mA. 40 VDC rating | AC Input failure |
4 | Signal Common | Signal Common |
5 | Output: Open collector transistor ON. SO mA. 40 VDC rating | Impending low battery |
6 | Input: RS232 level low (-12V) | Plug and Play software enable trigger |
7 | Input: Relay contact or RS232 level | Remote output OFF/ON: UPS total output can be kept off with low signal or closing relay contact |
8 | Output: 8 to 25 VDC, 5 W constant power (0.63 A max. @ 8V) | Auxiliary Control Power |
9 | Chassis | Connection to chassis |
|
|