Lightning-proof installation

Lightning-proof and protection from atmospheric electric is ensured by:

- installing lightning-rod;

- installing metallic grounded cells around outside objects;

- grounding facilities inside the building;

- making electric connection among close metallic elements of the building, such as pipelines, and grounding them.

Protection from lightning stroke is made with separate lightning-rods or ropes set on building.

Lightning-rods are selected in accordance to building’s plan. Lightning-rods of objects referred to category I are not set on the building however they should have dielectric stand 8 m above the building, grounding resistance up to 10 ohm and be situated 8 m as nearest. Grounding resistance is to be 20 ohm as maximum in category III.

To protect buildings and structures referred to categories II and III from lightning stroke lightning-rods are set separately or on the building as not insolated rods and ropes, or as metallic cell made from wire of 6-8 mm in diameter.

Connecting nearly situated metallic components of building, such as pipelines, in the places where less 10 cm is between them along every 20 - 25 m prevents electric induction. Resistance of that connection should be 0.03 ohm as maximum.

Grounding metallic parts of communication and other systems prevents transferring high electric potential inside building.