Emergency operation mode of electrical network

 

Consider the situation where one of the mains phases (phase C) withdrew to ground via a relatively low resistance Rg, such as wire breakage and falling to the ground. The network diagrams (see Fig. 8.3), this fact will be reflected in parallel with YC conductivity Y g = 1/ R g (Y gis not shown). Consequently, between phase C and ground conductivity be YС + Y g. Accordingly, the expression (8.8) takes the form:

          (8.21)

 

Three-phase four-wire network with earthed neutral:

Condition (8.9) is usually performed in the network, so the expression (8.21) can be simplified:

                        (8.22)

Considering the relation (8.5), and R 0<< Rh we obtain:

                           (8.23)

Three-phase three-wire network with isolated neutral:

For a thisnetwork YN = Y 0= 0. In addition, usually | YA|, | YB|, | YC |<< Yзм. Then the expression (19) takes the form:

                             (8.24)

or, given the expressions for a and relations (8.5)

Ih= U ph /(Rh + R g ) = U l/ (Rh + R g ).                         (8.25)

 

In emergency mode, often have a situation in which Rg substantially more R0 and simultaneously Rg << Rh. Under this condition, a comparative analysis of the formulas (21) and (23) shows that a person is under tension Uc close to a linear network with isolated neutral, which is more dangerous than the network with earthed neutral, where Uc approaching the phase voltage. For both types of networks is characterized by a decrease in risk of electric shock by increasing the Rh.

 


Понравилась статья? Добавь ее в закладку (CTRL+D) и не забудь поделиться с друзьями:  



double arrow
Сейчас читают про: